Sticker said 6.75oz and i did vacum test 30 minutes stay -28 .iam not sure if i make mistakes breezing with 15 % silver with out nitrogen flow.i put lot money in and now customer not happy is not cooling.
-
How is the frost pattern on the evaporator? Is it balling up with ice , is whole evap lightly frosted up?
-
Nothing
-
I will trying one more time i will text you for an hour
-
When you turn the unit off, see if the pressures equalize with in 15 mins. Low and height side should equalize.
-
I got it high pressure line after filter was plug.i will never use again Stay brite#8 onlyone place i used after filter..when i changed new line 20 inc and brazing with siver 15 i got pressure 0 psi and high side 105 psi evaporators start frost patern..
-
Thanks for help
-
Glad you got it! Weird pressures for a restriction, but it sounds like it’s good to go now.